Combined Synopsis/Solicitation
NAICS 333912
AIR COMPRESSOR CHILLER
CHILLER UNIT COMPONENTS FOR 760 CFM SULLAIRE AIR COMPRESSOR1 Model AFC44CB-0C41 General Air Products, Inc. Fluid Cooler at 427,538 Btu/Hr total at a flow of 46.4 gpm total with a 5? F approach, 40% propylene glycol solution and a design ambient of 85? F. Coolers will have A350 Johnson controls for fan cycling and 460v/3/60Hz electrical equipment and offer the following features as standard 4 direct drive 1.5 HP propeller fans with vinyl coated fan guards, weather resistant motors with sealed bearings, internal overload protection, and hardware designed for outdoor duty. Access door panels at each fan motor, vent and drain connection and corrosion resistant construction.1 Model FPSBD44A, 3 HP Fluid Pumping Station for 40 PSI and to be wired 460v/3/60Hz with a 120v control circuit. Pumping station to be completely pre-plumbed and pre-wired with TEFC type motors and a NEMA 4 steel control panel. The unit will have a close-coupled centrifugal pump with expansion tank, temperature and pressure gauges, check valves and shut off safety valves plus a steel base as standard. This unit will be a Duplex design.1 Model MVD75, 1.5? 75 degree thermostatic mixing valve.1 TC3060, Trim Cooler, to t...